產(chǎn)品詳情
Detailed inbation for: PSTX30-600-70
This page contains technical data sheet, documents library and bs to offering related to this product. If you require any other inbation, please contact us using b located at the bottom of the page.
PSTX30-600-70
General Inbation
-
Global Commercial Alias:PSTX30-600-70
-
Extended Product Type:PSTX30-600-70
-
Product ID:1SFA898103R7000
-
ABB Type Designation:PSTX30-600-70
-
EAN:7320500501290
-
Catalog Debion:PSTX30-600-70 Softstarter
-
Long Debion:Softstarter PSTX30-600-70 for max 600V main voltage and 100 - 250V 50/60Hz control supply voltage.
Categories
- Products ? Drives ? Softstarters ? Softstarters ? PSTX Softstarters ? PSTX30
Ordering
-
Minimum Order Quantity:1 piece
-
Customs Tariff Number:85044090
Popular Downloads
-
Data Sheet, Technical Inbation:1SFC132009C0201
-
Instructions and Manuals:1SFC132081M0201
Dimensions
-
Product Net Width:150.000 mm
-
Product Net Height:314.000 mm
-
Product Net Depth / Length:194.000 mm
-
Product Net Weight:6.10 kg
Technical
-
Rated Operational Voltage:208 … 600 V AC
-
Rated Control Supply Voltage (Us):100 … 250 V AC
-
Rated Control Circuit Voltage (Uc):DC Operation 24 V
-
Rated Frequency (f):Main Circuit 50/60 Hz
-
Rated Operational Power - In-Line Connection (Pe):(230 V) 7.5 kW
(400 V) 15 kW
(500 V) 18.5 kW
-
Rated Operational Current - In-Line Connection (Ie):30 A
-
Rated Operational Power - Inside Delta Connection:at 230 V 12.5 kW
at 400 V 25 kW
at 500 V 30 kW
-
Rated Operational Current - Inside Delta Connection:52 A
-
Service Factor Percentage:100 %
-
Overload Protection:Build-in electronic overload protection
-
Integrated Electronic Overload:Yes
-
Adjustable Rated Motor Current Ie:30 ... 100 %
-
Starting Capacity at Maximum Rated Current Ie:4xIe for 10s
-
Ramp Time:1 ... 120 second [unit of time]
-
Initial Voltage During Start:10 ... 99 %
-
Step Down Voltage Special Ramp:100 ... 10 %
-
Current Limit Function:1.5 … 7.5 xle
-
Switch for Inside Delta Connection:Yes
-
Run Signal Relay:Yes
-
By-pass Signal Relay:Yes
-
Fault Signal Relay:Yes
-
Overload Signal Relay:Yes
-
Analog Outputs:0…10 V, 0…20 mA, 4…20 mA
-
Signal indication ready to start/standby ON (LED):Green
-
Signal indication running R (LED):Green
-
Signal indication protection (LED):Yellow
-
Signal indication fault (LED):Red
-
Communication:Built in Modbus interface, Anybus, FieldBusPlug (with adapter).
-
Degree of Protection:acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
-
Terminal Type:Cable Clamp
-
Connecting Capacity Main Circuit:Hole Diameter 8.5 mm
-
Connecting Capacity Control Circuit:Rigid 1x2.5 mm2
-
Connecting Capacity Supply Circuit:Rigid 1x2.5 mm2
-
Tightening Torque:Main Circuit 8 N·m
-
Product Main Type:PSTX30
Environmental
-
Ambient Air Temperature:Storage -40 ... +70 °C
Operation -25 ... +60 °C
-
RoHS Status:Following EU Directive 2002/95/EC August 18, 2005 and amendment
Certificates and Declarations (Document Number)
-
Declaration of Conbity - CE:2CMT005209
-
Environmental Inbation:2CMT005232
-
Instructions and Manuals:1SFC132081M0201
-
RoHS Inbation:2CMT005210
Container Inbation
-
Package Level 1 Width:230 mm
-
Package Level 1 Depth / Length:395 mm
-
Package Level 1 Height:280 mm
-
Package Level 1 Gross Weight:6.70 kg
-
Package Level 1 EAN:7320500501290
-
Package Level 1 Units:1 piece
Classifications
-
Object Classification Code:Q
-
ETIM 4:EC002572 - Electronic motor control and protection device
-
ETIM 5:EC002572 - Electronic motor control and protection device
- ETIM 6:EC002572 - Motor management device